
Supremacy Series
®
Reach-Ins Service and Installation Manual
For customer service, call (800) 733-8829 or (800) 723-8948, Fax (989) 773-3210, www.deleld.com
8
Supremacy Series
®
Reach-Ins Service and Installation Manual
9
For customer service, call (800) 733-8829 or (800) 723-8948, Fax (989) 773-3210, www.deleld.com
Location
Units represented in this manual are for indoor use only. Be sure the
location chosen has a oor strong enough to support the total weight
of the cabinet and contents. Allow for a total load of approximately
1000 pounds (450kg) per door section. Reinforce the oor if
necessary to provide for maximum loading. For the most efcient
operation, be sure to provide good air circulation inside and out.
Inside cabinet: Take care not to block air ow to the fans or heating
elements and allow space along the front, back and sides.
Outside cabinet: Be sure that the unit has access to ample air; avoid
hot corners and locations near stoves and ovens. Always provide a
minimum of 12 inches (30.5 cm) of clearance above the unit that is
open to the front.
If the doors need to be removed during installation: Remove top
hinge cover, remove screw with Allen wrench. Then remove the
spring tension nut, then the door can be lifted and removed.
Leveling
A level cabinet looks better and will perform better because the doors
will line up with the door frames properly, and the cabinet will not be
subject to unnecessary strain.
Unit Installation - Surface Mounted
Large cabinets should always be moved with extreme care and
caution.
The surface mounting installation method uses stainless steel ramps
to allow entry into the cabinet (one ramp provided with roll-in models,
two with roll-through models).
1. Install a minimum of 1” (2.5cm) of cork insulation (or equivalent)
in the space under the unit. The insulation should be recessed.
2. Set the unit in place and seal the oor.
3. Install ramp(s). On refrigerators or freezers, when the ramps are
properly installed, heat from the heater wire will be transferred to
the ramp to prevent condensation.
Electrical connection
Refer to the amperage data on pages 3-11 or the
serial tag data and your local code or the National
Electrical Code to be sure the unit is connected
to the proper power source. A protected circuit
of the correct voltage and amperage must be run
for connection of the supply cord or permanent
connection to the unit. The power must be
turned off and disconnected whenever performing
maintenance or repair functions.
Permanently connected units must be connected in
accordance with NEC Article 422 Appliances.
C-Disconnecting means. It is the responsibility of
the end user to provide the disconnect means to
satisfy the authority having jurisdiction.
Large cabinets should always be moved with
extreme care and caution.
INSTALLATION ROLL-INS AND ROLL-THROUGHS
Comentarios a estos manuales