F18 Series Service and Installation Manual
For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com
8
Pressure Control Settings
Factory recommended low-pressure control settings are:
HFC-404A refrigerators: 85psi (5.86bar) cut-in and 65psi
(4.48bar) cut-out to maintain
approximate interior temperature of
38°F (3°C).
Differential setting of 20psi (1.38bar).
HFC-404A freezers: 32psi (2.21bar) cut-in and 8psi (.552bar)
cut-out to maintain approximate
interior temperature of 0°F to 5°F
(-18°C to -15°C).
Differential setting of 24psi (1.65bar).
HFC-404A refrigerators with LiquiTec Rail:
20psi (1.38bar) cut-in and 10psi
(.689bar) cut-out
Differential setting of 10psi (.689bar)
Temperature control for LiquiTec Rail,
25°F (-4°C) cut in and 18°F (-8°C) cut-
out.
Pressure control settings are measured in pressure,
not temperature.
Operation
After turning the ON/OFF switch to ON the unit’s compressor
will begin operating. Delfield refrigerated bases are designed
to maintain an operational temperature of 36°F to 40°F (2°C to
4°C). Temperature in the salad top and refrigerated rail opening
is 33°F to 41°F (0°C to 5°C) with pans recessed 2” (5.1cm) on
a standard wrapped refrigerated rail or flush with the LiquiTec
option at 86°F (30°C) ambient room temperature. Freezer
bases are designed to maintain an operational temperature of
0°F (-18°C).
Do not place hot pans on/against the blue ABS liner.
Do not throw items into the storage area. Failure
to heed these recommendations could result in
damage to the interior of the cabinet or to the
blower coil.
Overloading the storage area, restricting the air
flow, and continuous opening and closing of the
doors and drawers will hamper the units ability to
maintain operational temperature.
Refrigerated rail units
Product in the rail should be removed to the refrigerated base
at the end of the day. This allows you to turn the rail off at night
to save energy and the rail will have time to defrost as needed.
It also helps maintain product quality. The standard wrapped
refrigerated units are controlled by the pressure control which
is set to maintain the proper rail temperature. An on/off switch
is also provided for the rail and is required to be shut off at
night. The rail switch shuts off the rail only. With a LiquiTec rail
a thermostat is provided to maintain rail temperature as well as
the rail on/off switch. The LiquiTec rail is required to be shut
off at night as well to allow for defrosting. To ensure product
quality in the rail it is recommended that product be rotated
every four hours.
If adding any item to the unit, be sure to keep
in mind the location of the refrigeration lines on
wrapped rail units. A refrigeration leak in a rail
is extremely difficult and costly to repair. In some
cases it cannot be repaired at all.